Power cables with plastic insulation of rated voltage 0.66, 1 and 3kV

(А)YY

PVC compound sheathed power cables with aluminum or copper cores Low-flammable PVC compound sheathed power cables with aluminum or copper cores and PVC compound insulation.
  • Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483.
  • Insulation 
made of PVC compound 
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)
  • Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section
  • Inner sheath 
PVC compound or low-flammable PVC compound
  • Metal screen 
copper tape or copper wires lapping (for cables of voltage 3kV)
  • Outer sheath 
PVC compound for cables, low-flammable PVC compound for cables
  • Application
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66, 1 and 3kV AC, 50 Hz, incl. overhead installation providing that solar radiation protection is ensured. 
(А)YY for single cabling in cable trays and industrial premises. For bunched wiring passive fire protection means implementation is mandatory. In case of single wiring cables are flame-retardant, for bunched wiring in cable trays, outdoor (open) electrical systems (cable bridges, cable walkways). In case of bunched wiring cables are flame-retardant.
  • Technical characteristics:
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С 

Min installation bending radius:
  • for single-core cables – 10 times of cable OD 
  • for multi-core cables – 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2 
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years

(А)2XB2Y

XLPEinsulated armored power cables with copper or aluminum cores, with PE sheath 
XLPEinsulated armored power cables with copper or aluminum cores, with PE sheath, with water-blocking elements

  • Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483
  • Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)
  • Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section.
In cables insulated conductors are twisted and form the core around water-blocking yarns harness. Water-blocking tape covers the core with overlap
Inner sheath made of PVC compound
Armoring two steel zinc plated bands
Sheath made of PE
  • Application
for electrical energy transmission and distribution in stationary installations with rated voltage 660V AC, 1000V AC and 3000V AC, 50 Hz;
to be in ground in soil (raceways) independent from soil and ground water corrosivity, except for heaving and collapsible soils, as well as for cabling in soils with high soil dampness and for submarine cabling.
  • Technical characteristics
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69 
Operating temperature range from -60°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -20°С 

Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path: 
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years

(A)YBY

PVC compound insulated armored power cables with copper or aluminum cores, with cold-resistant PVC compound sheath 
PVC compound insulated armored power cables with copper or aluminum cores, with cold-resistant low-flammable PVC compound sheath
  • Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483 
  • Insulation 
made of PVC compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)
  • Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section.

Inner sheath 
PVC & low-flammable PVC compound 
Armoring two steel zinc plated bands 
Sheath cold-resistant PVC compound & cold-resistant low-flammable PVC compound 
  • Application
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66; 1 and 3kV AC, 50 Hz, in areas with cold climate, incl. overhead installation providing that solar radiation protection is ensured.
  • Technical characteristics
Cables climatic category is cold climate, placement category 1-4 as per GOST 15150-69 
Operating temperature range from -60°С to +40°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С 

Min installation bending radius: 
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path: 
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years

(A)2XCWY

XLPE insulated and low-flammable PVC compound sheathed, screened power cables with copper or aluminum cores.
  • Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483 
  • Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)
  • Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section 

Inner sheath made of low-flammable PVC compound 
Metal screen copper tape or copper wires lapping 
Thermal barrier glass tapes lapping 
Outer sheath made of low-flammable PVC compound 
  • Application 
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66, 1 and 3kV, 50 Hz. Cables are intended for general purpose industrial applications in the domestic market and for export. Cables are intended for bunched wiring in cable trays and buildings.
  • Technical characteristics
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С 

Min installation bending radius: 
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path: 
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 50% 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)2ХН

XLPE insulated and halogen-free PVC compound sheathed power cables with copper or aluminum cores.

Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section 

Inner sheath halogen-free polymer compound. 
Metal screen copper tape or copper wires lapping (for cables of voltage 3kV) 
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electrical wiring in offices equipped with PC and microprocessor technology, in kindergartens, schools, hospitals, shopping malls, underground premises, for cable lines of entertainment centers and sport facilities.
Technical characteristics
Cables climatic category is W, placement category 3 and 4 as per GOST 15150-69 
Operating temperature range from -30°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С 

Min installation bending radius: 
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)2ХСН


XLPE insulated and halogen-free PVC compound sheathed, screened power cables with copper or aluminum cores.

Conductor
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath halogen-free polymer compound
Metal screen copper tape or copper wires lapping
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electrical wiring in offices equipped with PC and microprocessor technology, in kindergartens, schools, hospitals, shopping malls, underground premises, for cable lines of entertainment centers and sport facilities.
Technical characteristics
Cables climatic category is W, placement category 3 and 4 as per GOST 15150-69
Operating temperature range from -30°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С

Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years

HXH-FE 180

Halogen-free polymer compound insulated and sheathed, fire-proofed power cables with copper cores.

Conductor
copper, single- or multi-wire, round or sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Thermal barrier lapping of two micaceous tapes

Insulation halogen-free polymer compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
twisted insulated cores of two-, three-, four- and five-core cables. All the cable's cores shall be of the same cross-section. In four-core cables one core (grounding or neutral) of smaller cross-section is allowed

Inner sheath halogen-free polymer compound
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electric wirings of fire protection systems (fire alarm system's circuits, fire-water pump's supply circuit, fire escape lightening, circuits of smoke exhaust system and forced ventilation, evacuation lift).
  • for electrical wirings of hospitals' surgery unit, circuits of emergency power supply and power supplying of equipment (load using equipment) used at fire. Cables are designed for bunched wiring.
Technical characteristics
Cables climatic category is W, placement category 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path 50 N/mm2 
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Cable flame-resistance - is the ability to function during and after flame source application during 180 minutes 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

2XCH-FE 180

XLPE insulated and halogen-free PVC compound sheathed, fire-proofed, screened power cables with copper cores.

Conductor
copper, single- or multi-wire, round or sectoral shape, conforming to Class 1 or 2 as per GOST 22483
Thermal barrier lapping of two micaceous tapes

Insulation made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
twisted insulated cores of two-, three-, four- and five-core cables. All the cable's cores shall be of the same cross-section. In four-core cables one core (grounding or neutral) of smaller cross-section is allowed

Inner sheath halogen-free polymer compound
Thermal barrier glass tapes lapping
Metal screen copper tape or copper wires lapping
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electric wirings of fire protection systems (fire alarm system's circuits, fire-water pump's supply circuit, fire escape lightening, circuits of smoke exhaust system and forced ventilation, evacuation lift)
  • for electrical wirings of hospitals' surgery unit, circuits of emergency power supply and power supplying of equipment (load using equipment) used at fire. Cables are designed for bunched wiring.
Technical characteristics
Operating temperature range from -50°С to +50°С
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path 50 N/mm2 
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Cable flame-resistance - is the ability to function during and after flame source application during 180 minutes 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(A)YBY

PVC compound insulated armored power cables with copper or aluminum cores, with PVC compound sheath 
PVC compound insulated armored power cables with copper or aluminum cores, with low-flammable PVC compound sheath

Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483
Insulation made of PVC compound

Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath PVC compound for cables, low-flammable PVC compound
Armoring two steel zinc plated bands
Sheath PVC compound & low-flammable PVC compound

Application
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66; 1 and 3kV AC, 50 Hz, incl. overhead installation providing that solar radiation protection is ensured. (A)YBY for single cabling in cable trays and industrial premises. For bunched wiring passive fire protection means implementation is mandatory. In case of single wiring cables are flame-retardant, for bunched wiring in cable trays, outdoor (open) electrical systems (cable bridges, cable walkways). In case of bunched wiring cables are flame-retardant.

Technical  characteristics:
Operating temperature range from -50°С to +50°С
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

N(А)2XBY


XLPEinsulated armored power cables with copper or aluminum cores, with PVC compound sheath. 
XLPEinsulated armored power cables with copper or aluminum cores, with low-flammable PVC compound sheath.

Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath PVC compound & low-flammable PVC compound
Armoring two steel zinc plated bands
Sheath PVC compound & low-flammable PVC compound

Application
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66; 1 and 3kV AC, 50 Hz, incl. overhead installation providing that solar radiation protection is ensured.

Technical characteristics
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)YCY

PVC compound sheathed and insulated power cables with aluminum or copper cores, screened Low-flammable PVC compound sheathed power cables with aluminum or copper cores and PVC compound insulation, screened.

Conductor
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of PVC compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath PVC compound & low-flammable PVC compound
Metal screen copper tape or copper wires lapping
Outer sheath PVC compound & low-flammable PVC compound

Application
Cables are intended for electrical energy transmission and distribution in stationary installations with high degree of electrical protection with rated voltage 0.66 and 1kV, 50 Hz.

Technical characteristics
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)НХМН

Halogen-free polymer compound insulated and sheathed power cables with copper or aluminum cores.

Conductor
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483.

Insulation 
halogen-free polymer compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath halogen-free polymer compound
Metal screen copper tape or copper wires lapping (for cables of voltage 3kV)
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electrical wiring in offices equipped with PC and microprocessor technology, in kindergartens, schools, hospitals, shopping malls, underground premises, for cable lines of entertainment centers and sport facilities.
Technical characteristics
Cables climatic category is W, placement category 3 and 4 as per GOST 15150-69
Operating temperature range from -30°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)2ХВН

XLPE insulated, armored power cables with copper or aluminum cores, with halogen-free PVC compound sheath.

Conductor
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath halogen-free polymer compound
Armoring two steel zinc plated bands
Outer sheath made of flame-retardant halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electrical wiring in offices equipped with PC and microprocessor technology, in kindergartens, schools, hospitals, shopping malls, underground premises, for cable lines of entertainment centers and sport facilities.
Technical characteristics
Cables climatic category is W, placement category 3 and 4 as per GOST 15150-69
Operating temperature range from -30°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

2ХH-FE 180

XLPE insulated and halogen-free PVC compound sheathed, fire-proofed power cables with copper cores.

Conductor
copper, single- or multi-wire, round or sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Thermal barrier lapping of two micaceous tapes

Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
twisted insulated cores of two-, three-, four- and five-core cables. All the cable's cores shall be of the same cross-section. In four-core cables one core (grounding or neutral) of smaller cross-section is allowed

Inner sheath halogen-free polymer compound
Thermal barrier glass tapes lapping
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electric wirings of fire protection systems (fire alarm system's circuits, fire-water pump's supply circuit, fire escape lightening, circuits of smoke exhaust system and forced ventilation, evacuation lift).
  • for electrical wirings of hospitals' surgery unit, circuits of emergency power supply and power supplying of equipment (load using equipment) used at fire. Cables are designed for bunched wiring.
Technical characteristics
Cables climatic category is W, placement category 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path 50 N/mm2 
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40% 
Cable flame-resistance - is the ability to function during and after flame source application during 180 minutes 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)2XY

XLPE insulated and PVC compound sheathed power cables with copper or aluminum cores. 
XLPE insulated and low-flammable PVC compound sheathed power cables with copper or aluminum cores.

Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath PVC compound & low-flammable PVC compound
Metal screen copper tape or copper wires lapping (for cables of voltage 3kV)
Outer sheath PVC compound & low-flammable PVC compound

Application
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66, 1 and 3kV AC, 50 Hz, incl. overhead installation providing that solar radiation protection is ensured.

Technical characteristics
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)YY

Power cables with aluminum or copper cores, PVC compound insulation, cold-resistance PVC compound sheath and cold-resistant low-flammable PVC compound sheathed power cables with aluminum or copper cores and PVC compound insulation.

Conductor
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of PVC compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath PVC compound & low-flammable PVC compound
Metal screen copper tape or copper wires lapping (for cables of voltage 3kV)
Outer sheath cold-resistant PVC compound & cold-resistant low-flammable PVC compound

Application
Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66; 1 and 3kV AC, 50 Hz, in areas with cold climate, incl. overhead installation providing that solar radiation protection is ensured.

Technical characteristics
Cables climatic category is cold climate, placement category 1-4 as per GOST 15150-69
Operating temperature range from -60°С to +40°С 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С 
Cable conductor allowable heating during overload is no more than +90°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)2XCY

XLPE insulated and PVC compound sheathed, screened power cables with copper or aluminum cores. 
XLPE insulated and low-flammable PVC compound sheathed, screened power cables with copper or aluminum cores.

Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
made of silane cross-linked PE
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath PVC & low-flammable PVC compound for cables
Metal screen copper tape or copper wires lapping
Outer sheath PVC compound & low-flammable PVC compound

Application
Cables are intended for electrical energy transmission and distribution in stationary installations with high degree of electrical protection with rated voltage 0.66 and 1kV, 50 Hz.

Technical characteristics
Cables climatic category is NF and T, placement category 1 & 5 as per GOST 15150-69 
Operating temperature range from -50°С to +50°С 
Ambient relative humidity at +35°С up to 98% 
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +90°С 
Cable conductor allowable heating during overload is no more than +130°С 
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +250°С 
Guarantee service life is 5 years (since cable commissioning) 
Service life is at least 30 years.

(А)НХВН

Halogen-free polymer compound insulated armored power cables with copper or aluminum cores, with halogen-free polymer compound sheath.

Conductor 
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483.

Insulation 
halogen-free polymer compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath halogen-free polymer compound
Armoring two steel zinc plated bands
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electrical wiring in offices equipped with PC and microprocessor technology, in kindergartens, schools, hospitals, shopping malls, underground premises, for cable lines of entertainment centers and sport facilities.
Technical characteristics
Cables climatic category is W, placement category 3 and 4 as per GOST 15150-69
Operating temperature range from -30°С to +50°С
Ambient relative humidity at +35°С up to 98%
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С
Cable conductor allowable heating during overload is no more than +90°С
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40%
Guarantee service life is 5 years (since cable commissioning)
Service life is at least 30 years.

(А)НХСН

Halogen-free polymer compound insulated and sheathed, screened power cables with copper or aluminum cores.

Conductor
copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Insulation 
halogen-free polymer compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section

Inner sheath halogen-free polymer compound
Metal screen copper tape or copper wires lapping
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electrical wiring in offices equipped with PC and microprocessor technology, in kindergartens, schools, hospitals, shopping malls, underground premises, for cable lines of entertainment centers and sport facilities.
Technical characteristics
Cables climatic category is W, placement category 3 and 4 as per GOST 15150-69
Operating temperature range from -30°С to +50°С
Ambient relative humidity at +35°С up to 98%
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path:
  • for aluminum-core cables – 30 N/mm2
  • for copper-core cables – 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С
Cable conductor allowable heating during overload is no more than +90°С
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40%
Guarantee service life is 5 years (since cable commissioning)
Service life is at least 30 years.

HXCH-FE 180

Low-flammable PVC compound insulated and sheathed, fire-proofed, screened power cables with copper cores.

Conductor
copper, single- or multi-wire, round or sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Thermal barrier lapping of two micaceous tapes

Insulation 
made of low-flammable PVC compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
twisted insulated cores of two-, three-, four- and five-core cables. All the cable's cores shall be of the same cross-section. In four-core cables one core (grounding or neutral) of smaller cross-section is allowed

Inner sheath made of low-flammable PVC compound
Metal screen copper tape or copper wires lapping
Outer sheath made of low-flammable PVC compound

Application
  • for electrical energy, as well as electrical signals, transmission and distribution in stationary installations with rated voltage 660 and 1000V AC, up to 100 Hz, and 1000 and 1500V DC, respectively.
  • for electric wirings of fire protection systems (fire alarm system's circuits, fire-water pump's supply circuit, fire escape lightening, circuits of smoke exhaust system and forced ventilation, evacuation lift)
  • for electrical wirings of hospitals' surgery unit, circuits of emergency power supply and power supplying of equipment (load using equipment) used at fire. Cables are designed for bunched wiring.
Technical characteristics
Cables climatic category is W, placement category 1-5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С
Ambient relative humidity at +35°С up to 98%
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С
Cable conductor allowable heating during overload is no more than +90°С
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40%
Cable flame-resistance - is the ability to function during and after flame source application during 180 minutes
Guarantee service life is 5 years (since cable commissioning)
Service life is at least 30 years.

HXCH-FE 180

Halogen-free polymer compound insulated and sheathed, fire-proofed, screened power cables with copper cores.

Conductor
copper, single- or multi-wire, round or sectoral shape, conforming to Class 1 or 2 as per GOST 22483

Thermal barrier lapping of two micaceous tapes

Insulation 
halogen-free polymer compound
Insulated cores of multicore cables have distinguishing color
Neutral cores insulation is blue
Grounding core insulation is two-color (yellow and green)

Twist 
twisted insulated cores of two-, three-, four- and five-core cables. All the cable's cores shall be of the same cross-section. In four-core cables one core (grounding or neutral) of smaller cross-section is allowed

Inner sheath halogen-free polymer compound
Metal screen copper tape or copper wires lapping
Outer sheath halogen-free polymer compound

Application
  • for electrical energy transmission and distribution in stationary installations with rated voltage 0.66 and 1kV AC, up to 100 Hz.
  • for electric wirings of fire protection systems (fire alarm system's circuits, fire-water pump's supply circuit, fire escape lightening, circuits of smoke exhaust system and forced ventilation, evacuation lift).
  • for electrical wirings of hospitals' surgery unit, circuits of emergency power supply and power supplying of equipment (load using equipment) used at fire. Cables are designed for bunched wiring.
Technical characteristics
Cables climatic category is W, placement category 5 as per GOST 15150-69
Operating temperature range from -50°С to +50°С
Ambient relative humidity at +35°С up to 98%
Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С
Min installation bending radius:
  • for single-core cables – 10 times of cable OD
  • for multi-core cables – up to 7.5 times of cable OD
Max allowable forces developed during cable pulling along the path 50 N/mm2
Continuous temperature of cable conductor heating during operation is +70°С
Cable conductor allowable heating during overload is no more than +90°С
Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С
Smoke released in test chamber during cables burning and smouldering does not decrease light permeability more than 40%
Cable flame-resistance - is the ability to function during and after flame source application during 180 minutes
Guarantee service life is 5 years (since cable commissioning)
Service life is at least 30 years.